Modbus RTU to BACnet/IP
One side polls RS-485 field devices as a Modbus RTU master, the other side exposes standard objects as a BACnet/IP server. Port 47808 by default, bindable to ETH0, with BBMD support for broadcast management across subnets.
The LM BACnet gateway is a core interconnect device in building automation systems: through protocol conversion and data mapping it brings Modbus devices onto the BACnet network, so equipment from different vendors is managed as one.

One side polls RS-485 field devices as a Modbus RTU master, the other side exposes standard objects as a BACnet/IP server. Port 47808 by default, bindable to ETH0, with BBMD support for broadcast management across subnets.
Supports AI, AO, AV, BI, BO, BV, MSI, MSO and MSV objects, with user-defined object instance numbers and BACnet standard engineering units for analog points, so a building controller reads and writes with a conventional point list and no private driver.
Covers the 0x / 1x / 3x / 4x data areas and supports bool, bit, bits, 8/16/32/64-bit integers, single- and double-precision floats and BCD, with four selectable byte orders (1234 / 4321 / 2143 / 3412).
Acquisition points support scaling and offset with y = ax + b engineering-unit conversion; read-write, read-only and write-only permissions are configured per point, and writable points can be written directly from the real-time data page.
Log in by entering the gateway IP in a browser, create a serial Modbus RTU channel, then add devices and points. The point table supports add, delete, clear, import and export, with no host software to install.
When acquisition goes offline, the BACnet side can set the value to 0 or hold the last good value, and the error state can be set to Out of service; a system point reports device online status to the building controller, while logs, serial traffic and ping tests isolate problems layer by layer.